Запис Детальніше

ВДОСКОНАЛЕННЯ МЕТОДІВ КОНТРОЛЮ І3ОЛЯЦІЇ МЕРЕЖ ОПЕРАТИВНОГО ПОСТІИНОГО СТРУМУ

Електронний архів E-archive DonNTU – (Electronic archive Donetsk National Technical University)

Переглянути архів Інформація
 
 
Поле Співвідношення
 
Title ВДОСКОНАЛЕННЯ МЕТОДІВ КОНТРОЛЮ І3ОЛЯЦІЇ МЕРЕЖ ОПЕРАТИВНОГО ПОСТІИНОГО СТРУМУ
Совершенствование методов контроля изоляции сетей оперативного постоянного тока
Improvement of Methods For Isolation Control of DC Networks
 
Creator ЖУК, І.А.
ЖУК, И.А.
ZHUK, I.
РУБАНЕНКО, О.Є.
РУБАНЕНКО, О.Е.
RUBANENKO, A.
 
Subject мережі оперативного постійного струму
опір ізоляції
метод
математична модель
генератор сигналу
сети оперативного постоянного тока
сопротивление изоляции
метод
математическая модель
генератор сигнала
network of DC
insulation resistance
the method
the mathematical model
the signal generator
 
Description Discussed the importance of networks of DC
power in the context of a variety of consumers of electric power stations and substations. Describes the insulation
momtoring device networks of DC, among which are the bridge circuits and circuits with the imposition of an
additional signal generator. Provide an improved method for deterrnimng the damaged line in the networks of DC
(OPT) by applying a signal of two different frequencies of the additional generator. Under this method, in the article the
developed mathematical model describing the state of networks, based on which one can find the values of the
resistance line to ground through frequency ratio test signals and the input impedance network of DC. Also proposed to
enhance the accuracy of the scheme to introduce special sensors, the calculation of the currents and voltages are
possible in the proposed mathematical model. In addition to the research paper presents the characteristics of the device
resistance momtoring network with respect to the poles of the earth on the basis of a mathematical model. To do this,
we study dependence of the relative errors of the resistance as a function of changes in the characteristics of the
network: the capacity of the lines, the frequency ratio, capacitance coupling capacitor, the resistance to ground, the
EMF source test signal of variable frequency. A formula calculated resistance, the data entered in the appropriate table,
as well as built plot of error depending on the resistance. Calculations have shown that, with sufficient accuracy of the
input data (the values of test current to the ground and the respective voltage drops across the resistor network pole to
ground), you can accurately determine the value of the resistance to earth and so to track the emergence of dangerous
drops it in a controlled network. Thus given research has proven the ability to control operating current networks based
on the proposed method.
Досліджено пристрої контролю ізоляції мереж оперативного постійного струму. Запропоновано вдосконaлити метод визначення пошкодженої лінії в мережax оперативного постійного струму (ОПС) за допомогою накладання сигналу трьох різниx частот від додаткового генератора. Ha основі вищезгаданого розроблено матeматичну модель пристроєм контролю активного опору полюсів мережі оперативного постійного струму (МОПС) відносно землі. Також досліджено характеристики приладу контролю опору полюсів мережі відносно землі на основі математичної моделі.
 