ДОСЛІДЖЕННЯ ТЕХНІЧНОГО СТАНУ ІЗОЛЯЦІЇ ОБМОТКИ СТАТОРА СИНХРОННОГО ГЕНЕРАТОРА В ПРОЦЕСІ ИОГО ЕКСПЛУАТАЦІІ
Електронний архів E-archive DonNTU – (Electronic archive Donetsk National Technical University)
Переглянути архів ІнформаціяПоле | Співвідношення | |
Title |
ДОСЛІДЖЕННЯ ТЕХНІЧНОГО СТАНУ ІЗОЛЯЦІЇ ОБМОТКИ СТАТОРА СИНХРОННОГО ГЕНЕРАТОРА В ПРОЦЕСІ ИОГО ЕКСПЛУАТАЦІІ
Исследование технического состояния изоляции обмотки статора синхронного генератора в процессе его эксплуатации Investigation of the Technical Condition of Stator Winding Insulation of the Synchronous Generator During Its Operation |
|
Creator |
КУТІН, В.М.
КУТИН, В. М. KUTIN, V. ШПАЧУК, О.О. ШПАЧУК, А. А. SHPACHUK, A. |
|
Subject |
синхронний генератор
обмотка статора технічний стан ізоляціії синхронный генератор обмотка статора техническое состояние изоляции synchronous generator stator winding technical condition of insulation |
|
Description |
Modern methods of diagnosing and relaying should allow early detection of damage, and to prevent the release of main equipment of power stations down. Failure as a result of injuries powerful hydro and turbogenerators in a small reserve of power grid is able to cause an avalanche of frequency of system failure, which in turn entail considerable material losses. It is therefore urgent task is to develop new and improve existing means of diagnosing and relaying powerful hydro and turbogenerators. For the development of new devices for diagnostics and protection necessary to identify the causes of the most common types of injuries. In the operation of the stator winding insulation powerful synchronous generator affected a large number of factors that impair its electrical properties. The quality of the insulation effect, as technology manufacturing, installation and maintenance of isolation, and processes in insulating materials and modes of synchronous generator. Construction of diagnosing the technical condition of the stator winding insulation synchronous generator, which would take into account the impact of the above factors are extremely difficult task due to the complexity of building subsystems collection and its high cost. Proposed for the purpose of relaying the stator winding synchronous generator, working in alliance with transformer, from single-phase earth fault and diagnosing the technical condition of the stator winding insulation synchronous generator use integral index - namely, the amount of current leakage through the insulation of the stator winding synchronous generator I = f (U; Rsw; Rt; C). The indexes characterize as the generator mode and state of the main parameters of the stator winding insulation (insulation resistance of the stator winding Rsw, stator winding insulation capacity relative to the ground C and transitional resistance in place of earth fault Rt). Using the proposed indicator can build systems that combine the functions of the device diagnostics and device relaying. Such protection can perform two-stage. The first level of protection will work on symmetric signal with a gradual decrease in the level of insulation below the set value, and the other in the event of sudden ground fault. В роботі розглянуто основні фактори та процеси, що впливають на зміну технічного стану ізоляції обмотки статора синхронного генератора відносно землі в процесі його експлуатації Запропоновано в якості показника якості функціонування ізоляції обмотки статора синхронного генератора використовувати значення струму витоку на землю. |
|
Date |
2013-11-01T12:17:26Z
2013-11-01T12:17:26Z 2013 |
|
Type |
Article
|
|
Identifier |
Наукові праці Донецького національного технічного університету. Серія "Електротехніка і енергетика". № 2 (15), 2013 р., 338 с.
http://ea.donntu.edu.ua/handle/123456789/23510 |
|
Relation |
Электротехника и энергетика;
|
|
Publisher |
ДонНТУ
|
|