Запис Детальніше

ОЦІНКА ЕФЕКТИВНОСТІ ЗАМИКАННЯ ПОШКОДЖЕНОЇ ФАЗИ МЕРЕЖІ НА ЗЕМЛЮ ЯК ЗАСОБУ ПІДВИЩЕННЯ ЕЛЕКТРОБЕЗПЕКИ ДІЛЬНИЧНОЇ МЕРЕЖІ ШАХТИ НАПРУГОЮ 3 (3,3) кВ

Електронний архів E-archive DonNTU – (Electronic archive Donetsk National Technical University)

Переглянути архів Інформація
 
 
Поле Співвідношення
 
Title ОЦІНКА ЕФЕКТИВНОСТІ ЗАМИКАННЯ ПОШКОДЖЕНОЇ ФАЗИ МЕРЕЖІ НА ЗЕМЛЮ ЯК ЗАСОБУ ПІДВИЩЕННЯ ЕЛЕКТРОБЕЗПЕКИ ДІЛЬНИЧНОЇ МЕРЕЖІ ШАХТИ НАПРУГОЮ 3 (3,3) кВ
Оценка эффективности замыкания поврежденной фазы сети на землю как средства повышения электробезопасности участковой сети шахты напряжением 3(3,3) кВ
Evaluation of damaged network phase circuit to earth as a means to improve electrical safety of a precinct network of a mine with voltage 3 (3,3) kV
 
Creator Руссіян, С.А.
Руссиян, С.А.
Russijan, S.
 
Subject шахта
електромережа
виток струму на землю
безпека
напруга
замикання
электросеть
утечка тока на землю
поврежденная фаза
напряжение
замыкание
leakage current
protection device
transformer substation
power network
electrical shock
 
Description The need of using 3 (3.3) kV equipment in coal mine section is determined by coal production increasing. Increasing the supply voltage from 1140V up to 3 (3.3) kV increases the probability of negative consequences of accidents in the electrical complexes of mine sections. Existing automatic protective devices of AZUR series for 1140V networks reveal earth leakage, compensate the capacitive components of leakage current, provide automatic safety shutdown of voltage of the network and ground fault of the damaged network phase. Taking into account the significant increase of leakage current values in the network with voltage 3 (3.3) kV as compared to the network 1140, the task of identifying relevant features of the implementation of these protective functions in higher voltage networks is significant. Today there are effective ways to identify the faulty phase in isolated neutral power network, many of which are used in networks of 1140 V. It is necessary to determine the characteristics of the use of such methods in the networks of 3 (3.3) kV. Study of transients in the system in case of curren tleakage to the ground is made using a computer model of the section power network, which allows calculating the instantaneous values of the current leakage to the ground and the total amount of electricity through the resistance of the leakage circuit. The simulation produced graphics that allow estimating the effectiveness of ground-fault faulted network phase as a way to improve electrical safety of 3 (3.3) kV power network. Several computational experiments were held, which resulted in conclusion, that in the absence of the faulted phase circuit closure on the ground total amount of electricity through the resistance of the circuit leakage is about 10 times greater than the maximum value, which is unacceptable. In the case of short-circuiting of the faulted phase on the ground the total amount of electricity is approximately 2 times greater than the maximum. To improve the efficiency of the faulty phase shorting it is offered to hold switchgear branches in the “on” state, thus reducing the total amount of electricity to 50% of the maximum allowable, that is reasonable. We also provided a single-phase equivalent circuit, which allows evaluating the effectiveness of faulted phase short-circuiting to earth in 3(3.3) kV net.
Проаналізовано ефективність замикання пошкодженої фази мережі на землю в контексті пошуку шляхів підвищення показників електробезпеки експлуатації дільничної електромережі напругою 3(3,3) кВ. Доведено доцільність примусового утримування комутаційних апаратів відгалужень у ввімкненому стані протягом затухання ЕРС асинхронних двигунів. Обґрунтовано універсальну однолінійну схему заміщення дільничної електромережі, що відображає всі етапи аварійного процесу при виникненні витоку струму на землю.
Проанализирована эффективность замыкания поврежденной фазы сети на землю в контексте поиска путей повышения показателей электробезопасности эксплуатации участковых электросетей напряжением 3(3,3) кВ. Доказана целесообразность принудительного удержания коммутационных аппаратов ответвлений во включенном состоянии до затухания ЭДС асинхронных двигателей. Обоснована однолинейная схема замещения участковой электросети, которая отображает все этапы аварийного процесса при возникновении утечки тока на землю.
 
Date 2014-08-27T17:21:21Z
2014-08-27T17:21:21Z
2014-06
 
Type Article
 
Identifier Наукові праці Донецького національного технічного університету. Серія: Обчислювальна техніка та автоматизація. Випуск 2(27). - Донецьк: ДонНТУ, 2014. - 229 с
2075-4272
http://ea.donntu.edu.ua/handle/123456789/27316
 
Relation Наукові праці Донецького національного технічного університету. Серія: Обчислювальна техніка та автоматизація. Випуск 2(27). - Донецьк: ДонНТУ, 2014. - С. 11-18.;
 
Publisher ДонНТУ